Abstract

In modern power systems with significant penetration of wind-turbines (WTs), improvement of low voltage ride through (LVRT) capability of WTs equipped with doubly-fed induction generators (DFIGs) is an important issue. Thus, this paper proposes a low voltage ride through (LVRT) strategy, which comprise of a capacitor connected in series with an inductor both connected in parallel to a resistor. The configuration is then connected to a small series resistor via a pair of antiparallel-Thyristors. The circuit and its switching control scheme of the proposed LVRT circuit are designed to: minimize the transition times, maintain the RSC connection to the rotor-windings, and reduce oscillations of dc-link voltage. In this case, the capacitor is entitled to eliminate ripples generated in the rotor voltage while the inductor reduces the ripple in rotor current. Different fault conditions were studied to validate the performance of the proposed scheme using MATLAB/Simulink platform. Comparative results and analysis are presented with conventional LVRT strategies.